FREQUENTLY ASKED QUESTIONS

JUST FIND YOUR ANSWERS BELOW

FAQ FOR COMMERCIAL AIR CONDITIONERS
What to do when evaporating pressure is too low?
————————————————————————————
Reason: It may be cool water not enough; or cool load low; or failure occurred at throttle orifice; or heat transfer at heat transfer tube of evaporator bad for the pollution like furring; or lack of refrigerant.
Solution: Check the cool water circuit and refill the cool water to rated volume; or check the rated temperature at auto on/off device; or check if expand throttle is blocked; or clean the heat transfer tube; or fill the refrigerant to needed volume.


What to do when condensing pressure is too high?
————————————————————————————
Reason: It may be cooling water not enough; or capacity of cooling tower reduced; or temperature of cool water too high; or cooling capacity too high to increase the load at condenser; or non condensed gas exist; or heat transfer at condensing tube bad for the pollution like furring.
Solution: Check the cool water circuit and adjust it to rated current flow; or check cooling tower and expand throttle etc. to lower (or rise) the temperature of cool water to rated temperature as soon as possible; or get rid of non condensed gas; or clean the tube.


What to do when the difference of oil pressure is too low?
————————————————————————————————
Reason: It may be oil filter blocked; or oil pressure adjusting valve (gate gurgle valve) opened too wide; or outlet oil at oil pump decreased; or bearing abrades; or failure occurred at oil pressure meter (or sensor); or too many refrigerant mixed into lubricating oil (oil pressure is too low for oil bubbles when starting).
Solution: Change the core of oil filter; or tighten the oil pressure adjusting valve so that the oil pressure rise to rated pressure; or disassembly to check; or change the bearing; or check oil pressure meter, reset the pressure sensor and change it when necessary; or do apply the oil heater when cooler stops to maintain rated oil temperature (check if wire of oil heater is breaking, and if the set temperature for oil heater to heat is correct).



What to do when cool water is subcool?
———————————————————————
Reason: It may be cool water not enough; or cool load low
Solution: Check the cool water circuit and refill cool water to rated volume; or wait for cool load rise.


Over load at oil pump
———————————————————————
Reason: It may be oil pump broken; or resistance at oil circuit too great.
Solution: Disassembly the oil pump to check; or check the oil circuit system like oil filter and other components, change them when necessary.


What to do when oil temperature is too high?
—————————————————————————
Reason: It may be cooling capacity of oil cooler lowered; or refrigerant supply for cooling oil cooler not enough for refrigerant filtering net is blocked; or bearing abrades.
Solution: Adjust oil temperature adjusting valve; or clean refrigerant filtering net; or disassembly to repair or change bearing.


What to do when water failure occur?
———————————————————————
Reason: It may be cooling water not enough; or failure at differential meter
Solution: Check cool water pump and cool water circuit and adjust to normal flow volume; or check and repair differential meter.


What to do when winding for main motor is superheat?
———————————————————————————————
Reason: It may be power phase voltage unbalance; or voltage drop at power cord large; or operating with ultra low head; or refrigerant supply for cooling main motor not enough for refrigerant filtering net is blocked.
Solution: Take measures to make power phase voltage balance; or take measures to lower voltage drop at power circuit; or clean the refrigerant filter net.

INCOMPLETE OF THE DISPLAY IN LCD
Fix the frame case well
—————————————
The LCD frame case is not fixed well
HEATING PERFORMANCE IS BAD
Abnormal of control circuitry
—————————————————
Contact the service center


The outdoor environment temperature is lower than -5℃
———————————————————————————————
Affect the function of air conditioner


Heat pharmaceutical leaks
———————————————
Contact service center


Room temperature is set too low to heat———————————————————————
Increase the set temperature


Doors or windows aren’t close well———————————————————————
Close the door or window to preserve cool (heat)


Air filter is dirty or blocked
———————————————
Clean filter to improve airflow
BIG OSCILLATION OR NOISE IS TOO LOUD
Screw is loose
—————————
Tighten the screw


There are foreign objects on the unit
————————————————————
Remove the foreign objects


Bracket of the unit is not installed steadily————————————————————————
Fix the bracket or reinstall it


Unit is not placed well
————————————————
Adjust the location of the units


Compressor is not installed well, or the floor stand is not firm enough——————————————————————————————————————
Check if the floor stand is firm
NO RESPONSE AFTER ENERGIZATION
Integrated modular CPU broken
——————————————————
Change integrated modular CPU


Cool joint or breakage at manostat 7806
———————————————————————
Change manostat 7806


Crystal oscillator or resetting circuit element is broken———————————————————————————————
Change them


Commutate diode is broken
———————————————
Change commutate diode


Transformer is broken
————————————
Change the transformer


Blow of the fuse
—————————
Change fuse
WIRELESS REMOTE CONTROLLER CAN’T RECEIVE SIGNAL (REMOTE CONTROL TYPE WINDOW UNIT)
Wireless remote controller has malfunction
—————————————————————————
Change wireless remote controller


Breakage or bad connecting of the receiving terminal
——————————————————————————————
Change receiving terminal or adjust connecting wire of receiving terminal


Receiving terminal is loose
———————————————
Adjust the receiving terminal


LCD FLASHES OR FULL SCREEN DISPLAY WHEN PRESSING THE TRANSMIT BUTTON
Change battery
—————————
Low battery
THE TREATMENT TAKEN BY PROTECTOR WHEN THE COMPRESSOR IS OVER HEATED
Protector is in error
—————————————————————————
Check if the contact points are connected by multimeter when the compressor is not over heated, if it isn’t connecting, change protector


Compressor cannot run smoothly, crankshaft jammed or breakage of discharge valve
——————————————————————————————
Change compressor


Capillary is blocked and inspiration temperature increases———————————————
Change capillary


Refrigerant is not enough or too much
———————————————
Adjust the amount of refrigerant



THE RECEIVING DISTANCE OF WIRELESS REMOTE CONTROLLER IS SHORT
Low battery
—————————
Change the battery
THE COMPRESSOR CAN’T STARTUP AFTER ENERGIZATION
Compressor is open-circuit or short-circuit
————————————————————————
Change compressor


Wrong wire connection
—————————————
Reconnect the wire


The main On/Off switch is broken
———————————————————
Change the main On/Off switch


Compressor capacitor is broken
———————————————
Change compressor voltage


Set temperature of temperature controller is too high or temperature controller is broken
————————————
Decrease the set temperature of temperature controller or change the temperature controller